HENSOTHERM® RM 30 / RM 50 / RM 100
Fire protection collar for single pipe lead-throughs in walls and floors
The HENSOTHERM® RM 30 / RM 50 / RM 100 fire protection collar is designed as a pipe seal to reinstate the fire safety of solid wall and floor structures provided with apertures for pipes and EIR / flexible pipes (with and without cabling).
Product characteristics
- ETA 20/1308 of 01/01/2021, tested in accordance with DIN EN 1366-3
- Approval for Switzerland VKF-No. 31642
- Fire resistance class up to EI 240
- Substrate: Solid walls and drywalls [thickness: ≥ 10 cm], solid floors [thickness: ≥ 15 cm]
- Applications: Combustible pipes with and without PE soundproofing, composite aluminium pipes, EIR / bundled flexible pipes, tube for wood pellets
- Installation with bolts or threaded rods (no plugs)
- Annular gap sealed with gypsum filler or cement mortar of building material class A1 according to DIN 4102
- Suitable for interior applications, wet rooms, and covered exterior spaces (with no driving rain!)
Advantages
- Combustible pipes up to DN 560 mm are covered by the ETA
- Flammable pipes tested with and without coupler
- Tested with and without PE soundproofing
- Double zero-gap applications on composite aluminium pipes
- Easy plugless installation
- High-quality stainless steel housing (rustproof)
Environment
- Contains no solvents, silicone, halogens, or plasticisers
- Green Product, VOC Emissions Class A+
- Fulfils the eco-bau 1 and Minergie-eco requirements